The ideal solution for simple 2 door “mantrap” applications.
Interlocking door systems in pharmaceutical and life sciences facilities often require a period of stabilization before users can fully pass through the system. The EZ ModLock 2-Door Timer Module brings precise, time-based control to your two-door interlock system so you can protect that period without adding complexity.
Space reconditioning is critical in cleanrooms and pharmaceutical settings for processes like:
When the first door closes, the timer automatically engages. The second door cannot be unlocked until the preset delay expires, usually between 0 and 60 seconds. The two-door system works exclusively on doors that are normally unlocked.
Common applications for the EZ ModLock 2-Door Timer Module include:
Interlock door systems prevent people from entering spaces before the environment has returned to specification, which is why visual cues like LED indicators are essential for improving workflow. Our module contains interactive LEDs, including a real-time door status indicator light and an electric lock status indicator. The visual feedback provides information about whether the door is open, locked or in a time delay, which makes it easier for operators to proceed safely.
The only applicable logic for a two-door mantrap is L1, also known as room logic. This logic ensures that whenever one door is open, the other door’s lock is actuated. A timer module complements this logic by ensuring that the second door remains locked until the environment behind it stabilizes.
The timer prevents the second door from opening too soon, even if the first door is already locked. On the rear of the module is a rotary timer switch and two DIP switches to set the desired door open/close scenario. You can choose which door or doors generate the time delay.
The EZ ModLock 2-Door Timer Module is part of our modular EZ ModLock line, which offers plug-and-play capabilities for manually operated door systems. It can be integrated with building management systems for centralized monitoring. It’s compatible with all electric failsafe locks and other devices operating at 24VDC, so you can save time and money on replacements.
Our systems are not compatible with access control systems or fire alarms, and they cannot be used on doors that are normally locked.
| Part Number | EZML2DTA1 |
| Power Requirements | 24VDC, 1.5 amps |
| Power Supply | UL Listed, 90-264VAC to 24VDC, 47-63Hz, 1.5A |
| Module Dimensions (H x W x D) | 3.75" x 4.25" x 1.5" (95 x 108 x 38mm) |
| Module Material | Plastic with integrated mounting ears |
| Connections | Door 1 and Door 2: Cat 5 cable with RJ45 connector BMS: Cat 5 cable with RJ45 connector |
| LED Indicators | Door status, electric lock status, door indicator status |
| Number of Doors Connected/Managed | 2/2 |
| Door Opening Logic | L1 |
| Door Opening Logic Programming | Qty 2 DIP switches |
| Recovery Time Programming | 1 settable rotary switch, 0-90 seconds in 10-second increments or 0-9 minutes in 1 minute increments |
| Door Initial State | Normally unlocked |
| Automated Door Management | No |
| Warranty | 2-year limited warranty |
Sentry Interlocks is dedicated to designing easy-to-install door interlocking systems highly regulated industries can rely on. You can also take advantage of our integration services to support proper installation and integration with the rest of your facility.
Our EZ ModLock 2-Door Timer Module presents a purpose-built solution to regulating traffic flow within your facility. Contact us online or call 267-369-1882 to discuss your door system needs and request a free quote.